山特3C3 UPS RS232通讯协议
PROTOCOL COMMAND
山特电子(深圳)有限公司
1 OF 1
Hardware : BAUD RATE . . . . . . . . . . . . DATA LENGTH . . . . . . . . . : STOP BIT . . . . . . . . . . . . . . PARITY . . . . . . . . . . . . . . . Commands :
Q2 WA
: 2400 bps 8 bits : 1 bits : NONE
Q2,XX WA,XX
Status inquiry 2 KW and KVA
S MMM.M MMM.M MMM.M NNN.N PPP.P PPP.P PPP.P QQQ QQQ QQQ RR.R SSS.S TT.T b7b6b5b4b3b2b1b0 Input Voltage: I/P fault voltage: Output Voltage: Output Current: I/P frequency: Battery voltage: Temperature: UPS Status: MMM.M M is an integer number 0 to 9. The Unit is Volt. Three Phases will represent Phase R-S-T in sequence NNN.N N is an integer number 0 to 9. The Unit is Volt. PPP.P P is an integer number 0 to 9. The Unit is Volt. Three Phases will represent Phase R-S-T in sequence QQQ QQQ is a percent of maximum current , not an absolute value. Three Phases will represent Phase R-S-T in sequence RR.R R is an integer number ranging from 0 to 9. The unit is Hz. SSS.S S is an integer number ranging from 0 to 9. TT.T T is an integer number ranging from 0 to 9. The unit is degree of centigrade. UPS status : byte Description 7 6 5 4 3 2 1 0 Stop Byte: 1 : Utility Fail ( Immediate ) 1 : Battery Low 1 : Bypass/Boost Active 1 : UPS Failed 1 : UPS Type is Standby (0 is On_line) 1 : Test in Progress 1 : Shutdown Active Reserved (always 0 ) KW and KVA command Computer: WA UPS: WWW.W WWW.W WWW.W VVV.V VVV.V VVV.V TTT.T SSS.S AAA.A AAA.A AAA.A QQQ b7b6b5b4b3b2b1b0 2 OF 2 The first of the UPS respond is very similar to the existing inquiry Q2 however Output power: WWW.W W is an integer number 0 to 9. The Unit is KW. R phase. Three Phases will represent Phase R-S-T in sequence Output complex power: Total power: VVV.V V is an integer number 0 to 9. The Unit is KVA. R phase. Three Phases will represent Phase R-S-T in sequence TTT.T T is an integer number 0 to 9. The Unit is KW. Include of three phase R,S,&T Total complex power: real power. SSS.S S is an integer number 0 to 9. The unit is KVA. Include of three phase R,S,&T complex power. Output current: AAA.A A is an integer number 0 to 9. The unit is A. R phase. Three Phases will represent Phase R-S-T in sequence O/P load: QQQ QQQ is maximum of W% or VA%. VA% is a percent of maximum VA. W% is a UPS Status: percent of maximum real power. b7b6b5b4b3b2b1b0 The same of Q2UPS status : Stop Byte: Shutdown command : Computer: S UPS: Shut UPS output off in The UPS output will be off in But if the battery under occur before After UPS shut down, the controller of UPS monitors the utility. If the utility is there, the UPS will wait for 10 seconds and connect the utility to output. 3 OF 3 因篇幅问题不能全部显示,请点此查看更多更全内容