10kV老旧分接箱更换改造工程等32项配网技术
改造工程(上册中压部分)
10kV欧式箱式变电站
(普通油浸式变压器、高供低计)
技术规范(专用部分)
2015年11月
目 次
1 标准技术参数表 ··········································································································· 1 2 项目需求 ···················································································································· 4 2.1 货物需求及供货范围 ···································································································· 4 2.2 必需的备品备件、专用工具和仪器仪表供货表 ········································································ 4 2.3 图纸提交单位 ············································································································ 5 2.4 工程概况 ················································································································· 5
2.5 使用条件 ················································································································· 5 2.6 可选技术参数表 ········································································································· 6
3 投标人提供信息 ··········································································································· 6 3.1 投标人技术偏差表 ······································································································· 6 3.2 销售运行业绩表 ········································································································· 6 3.3 推荐的备品备件、专用工具和仪器仪表供货表 ········································································ 7 3.4 主要组部件材料表 ······································································································· 7 3.5 投标人技术参数偏差表 ·································································································· 7 3.6 投标人应提供的其他资料 ······························································································· 8 3.7 投标人需提供的设备图纸及资料 ······················································································· 8
1 标准技术参数表
投标人应认真逐项填写技术参数响应表(见表1)中“投标人保证值”,不能空格,也不能以“响应”两字代替,不允许改动招标人要求值。如有偏差,请填写投标人技术参数偏差表(见表11)。
表1 技术参数响应表
序号 一 1 2 3 4 5 6 7 8 9 10 11 额定电压 额定频率 额定电流 温升试验电流 额定工频1min耐受电压(相对地) 额定雷电冲击耐受电压峰值 (1.2/50s)(相对地) 额定短路开断电流 额定短路关合电流 额定短时耐受电流及持续时间 额定峰值耐受电流 辅助和控制回路短时工频耐受电压 试验电压 12 局部放电 单个绝缘件 pC 电压互感器、电流互感器 名 称 单位 12kV开关柜 kV Hz A kV kV kA kA kA/s kA kV kV 标准参数值 投标人保证值 12 50 630(负荷开关+熔断器) 1.1Ir 42 75 31.5(熔断器) 50 20/4 50 2 1.1×12/3 ≤3 ≤10 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 控制回路 13 14 15 防护等级 隔室间 瓷质材料(对地) 16 17 18 19 20 21 22 23 爬电距离 有机材料(对地) 相间及相对地净距(带电体对门空气距离) SF6气体额定压力(20℃表压)(充气柜适用) SF6气体年漏气率 熔断器 电流互感器 电压互感器 氧化锌避雷器 供电电源 辅助回路 使用寿命 柜体外壳 V V 年 —— —— ≥20 IP4X IP2X ≥216 mm ≥240 mm V/V ≥155 0.04-0.05 ≤0.5% 见表6 —— —— HY5WZ-17/45 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 1
24 二 1 2 3 4 开关状态显示器 动态显示开关柜状态,并具有加热驱潮功能等其它必要辅助功能 投标人填写 变压器 型号 额定容量 分接范围 联接组别 高压绕组雷电冲击(全波) kVA S13 630 见表6 见表6 75 85 kV 高压绕组工频耐压 低压绕组工频耐压 35 5 K kW kW % 框架断路器(0.4kV) 型号 额定电流 额定工作电压 额定绝缘电压 极数 额定运行短路分断能力 额定峰值耐受电流 分闸时间 合闸时间 智能脱扣器选型 A V V kA kA ms ms 塑壳断路器(0.4kV) 型号 额定电流 额定工作电压 额定绝缘电压 A V V 55 按国标 按国标 按国标 1.5倍;2h 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 5 绝缘水平 高压绕组雷电冲击(截波) 6 7 8 9 10 三 1 2 3 4 5 6 7 8 9 10 四 1 2 3 4 油面温升限值 空载损耗 负载损耗 空载电流 短时过载能力 投标人填写 投标人填写 投标人填写 投标人填写 见表6 400 660 见表6 65 80 30 30 无 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 见表6 400 660 投标人填写 投标人填写 投标人填写 投标人填写 2
5 6 7 五 1 2 3 4 六 1 2 3 七 1 2 八 1 2 九 1 极数 额定运行短路分断能力 脱扣器选型 kA 电流互感器(0.4kV) 见表6 50 L 投标人填写 投标人填写 投标人填写 型号 变比 测量用CT精度 计量用CT精度 电容器(0.4kV) LMZJ1-0.66 1200/5 0.5 0.5S 投标人填写 投标人填写 投标人填写 投标人填写 型号 额定工作电压 额定容量 V kvar 低压母线 BSMJ0.4 400 180 投标人填写 投标人填写 投标人填写 母线材质 电流密度 A/mm2 铜母线,全部加装高压绝缘护套(包括分支母线) ≤0.9 投标人填写 投标人填写 —— —— (投标人填写) 低压防雷及浪涌保护器 型号 最大冲击电流峰值IIMP(10/350s) kA 箱变噪声水平 噪声水平 见表6 —— ≥75 附表1 标准参数表
变压器容调压高压 方式 (kV) 量 (kVA) 50 100 160 200 315 400 500 630 800 1000 1250 无励磁 10 ±2×2.5% 0.4 Dyn11 高压分接范围 低压 联结组(kV) 标号 空载 损耗 (kW) 0.13 0.20 0.28 0.34 0.48 0.57 0.68 0.81 0.98 1.15 1.36 空载 电流 (A) 1.60 1.44 1.28 1.20 1.12 1.04 0.96 0.88 0.80 0.80 0.72 负载损耗 (kW) 0.91/0.87 1.58/1.50 2.31/2.2 2.73/2.6 3.83/3.65 4.52/4.30 5.41/5.15 6.20 7.50 10.30 12.00 6.5 4.5 4.0 短路阻抗 (%) 3
1600 1.64 0.64 14.50 8 注 对于额定容量为500kVA及以下的变压器,表中斜线上方的负载损耗值适用于Dyn11联结组,斜线下方的负载损耗值适用于Yyn0联结组。
附表2 箱式变电站标准配置表
高压侧接线方式 变压器容量 终端型 630kVA 见箱变配置接线图 180kvar 低压出线回路 电容器容量 附表3
变压器容量(kVA) 100 160 200 315 500 630 800 1000 1250 2000 2500 轨距A×B(mm×mm) 550×550 550×550 660×550 660×660 660×660 820×820 820×820 820×820 1070×820 — — 声功率级(dB) 65 66 67 69 70 71 72 72 74 77 78 2 项目需求
2.1 货物需求及供货范围
货物需求及供货范围一览表见表2。
表2 货物需求及供货范围一览表
序号 设 备 名 称 单位 项目单位要求 规格 S13-M-630/10 配置见箱变配置接线图 —— 配置见箱变配置接线图 数量 1 1 —— 1 投标人响应 型号和规格 数量 1 2 3 4 欧式箱变 高压进线开关柜 高压计量柜 高压出线开关柜 套 面 面 面 http://bangbu.houbigangguan.com填写 投标人填写 投标人填写 投标人填写 4
5 6 7 8 9 10 电流互感器(0.4kV) 电容器(0.4kV) 无功补偿自动控制器(0.4kV) 低压防雷及浪涌保护器 附件(满足箱变运行所有部件) 只/套 组/套 套/套 只/套 套 配置见箱变配置接线图 配置见箱变配置接线图 配置见箱变配置接线图 —— 配置见箱变配置接线图 按需 按需 按需 —— 1 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写
2.2容量及数量: 箱变型式 欧式箱变 容量 S13-630kVA 数量 1 台 安装地点 户外
2.3 必备的备品备件、专用工具和仪器仪表供货表
必备的备品备件、专用工具和仪器仪表供货表见表3。
表3 必备的备品备件、专用工具和仪器仪表供货表
序号 1 2 3 名 称 熔断器 单位 只 项目单位要求 型号和规格 与进出线开关柜内熔断器同型号 数量 3 型号和规格 投标人响应 数量 生产厂 投标人填写 2.4 图纸提交单位
投标人提交的需经确认的图纸资料及其接收单位见表4。
表4 投标人提交的需经确认的图纸资料及其接收单位
提交图纸、资料名称 认可图、最终图、 (附电子文档) 认可图、最终图、 说明书、试验报告 (附电子文档) 接收图纸单位名称、地址、邮编、电话 乌海海金电力勘测设计有限责任公司 提交份数 8 乌海电业局 8 2.5 工程概况
1) 项目名称: 2) 项目单位: 3) 交通、运输:汽运 2.6 使用条件
使用条件见表5。
表5 使 用 条 件
序号 1 2 3 名 称 额定电压 最高运行电压 系统中性点接地方式 单位 kV kV 招标人要求值 10 12 不直接接地 5
4 5 额定频率 污秽等级 最高日温度 Hz ℃ 50 IV 40 35 最低日温度 6 环境温度 最大日温差 最热月平均温度 ℃ 最高年平均温度 7 8 9 10 11 12 13 日相对湿度平均值 湿度 % 月相对湿度平均值 海拔高度 太阳辐射强度 最大覆冰厚度 离地面高10m处,维持10min的平均最大风速 地面水平加速度 耐受地震能力 正弦共振三个周期安全系数 m W/cm2 mm m/s m/s2 K 25 +30 +20 ≤95 ≤90 1200 0.1 15 35 2 ≥1.67 户外 安装场所(户外) 注 1. 环境最低气温超过25℃的需要进行温度修正。 2. 污秽等级为Ⅳ级的需提供该地区的污秽等级图。 3. 有关海拔、污秽、温度的修正情况见表7。
4. 箱顶盖应有5%的坡度,顶盖不应积水,顶盖为可拆卸结构,满足吊装的要求。箱门应密封防水,应设置不
易被破坏、侵害的专用锁(暗锁);箱体外(不含基础)无外露可拆卸的螺栓。应充分考虑到自然通风的散热的方式,使风径通过热源,充分提高散热效率。变压器室内应具备强制排风措施,温度过高,则自动启动轴流风机向外排风,保证变压器工作在合理的温度范围内。
5. 箱体为阳极氧化锌防腐处理的合金板(板厚不小于http://baotou.houbigangguan.com的2.5mm),加保温材料,采用有高强度螺栓并应有良好的防松动措施,箱体应能长期承受50kPa表压,箱体应有防水、防凝露装置,箱体各门间要求装设联锁装置,箱体带有自动强制通风装置。
6.箱体内设有方便观察运行中设备的观察窗,观察窗应能看到进线柜接地开关分、合位置,设照明灯供观察、检修用。
7.本产品应采用45#克拉玛依油,注入变压器前应经过真空和机械过滤、脱气、脱水并去除杂质,其性能符合
GB-2536-1990、GB-7595-1987、SD187-1986等技术标准的规定。 8.箱变外形尺寸满足施工现场的需求。
2.7 可选技术参数表
可选技术参数表见表6。
表6 可选技术参数表
序号 1 2 3 项 目 高压侧接线方式 12kV负荷开关工位 高压熔断器额定电流 标准参数值 终端型/环网型 二工位/三工位 31.5A、40A、50A、63A 招标人要求值 终端型 二工位/三工位 63A 投标人保证值 投标人填写 投标人填写 投标人填写 6
4 5 6 7 8 9 10 11 12 13 14 15 16 17 变压器型号 变压器容量 变压器联接组别 变压器分接范围 变压器高压 绕组额定电压 变压器铁心材料 低压安装方式 电压母线材质 框架断路器(0.4kV)额定电流 框架断路器(0.4kV)极数 塑壳断路器(0.4kV)额定电流 塑壳断路器(0.4kV)极数 电流互感器变比(0.4kV) 箱变噪声水平 S—M—/10 S(B)H—M—/10 315kVA、400kVA、500kVA、630kVA Dyn11/Yyn0 ±5%、±(2×2.5%)、±(4×2.5%) 10/10.5 优质硅钢片/非晶合金, 卷铁心或叠片式结构 面板/柜体 铜排(电解铜)/母线系统 800A、1250A、1600A 3P、4P 200A、400A、630A 3P、4P 200/5、400/5、630/5、800/5、1250/5 45、50 S13—M-630/10 630kVA Dyn11 ±(2×2.5%) http://benxi.houbigangguan.com 优质硅钢片、卷铁心 柜体 铜排TMY-80*8配高压绝缘护套 1200A 3P 400A 3P 300/5、400/5、1200/5 45 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 投标人填写 3 投标人提供信息
3.1 投标人技术偏差表
投标人提供的产品技术规范应完全满足本技术规范中规定。若有偏差,投标人应如实、认真地在技术参数偏差表(见表11)中填写差异值,否则视为与本技术规范中规定的要求一致。若无技术偏差,则应在表11中填写“无差异”。
表7 项目单位技术偏差表(项目单位填写)
(本表是对本技术规范的补充和修改,如有冲突,应以本表为准) 序号 1 2 序号 1 2 项 目 …… 项 目 …… 标准参数值 变更条款页码、款号 项目单位要求值 原表述 投标人保证值 变更后表述 3.2 销售运行业绩表
销售运行业绩表(近5年)见表8。
7
表8 销售运行业绩表(近5年)
序号 1 2 3 4 5 6 7 型号规格 数量 用户单位 用户联系人 用户联系人电话 投运时间 备注 3.3 推荐的备品备件、专用工具和仪器仪表
推荐的备品备件、专用工具和仪器仪表供货表(投标人填写)见表9。
表9 推荐的备品备件、专用工具和仪器仪表供货表(投标人填写)
序号 1 2 3 名 称 型号和规格 单位 数量 3.4 主要组部件材料表
主要组部件材料表见表10。
表10 主要组部件材料表
产品型号 组部件名称 负荷开关 熔断器 变压器 避雷器 框架断路器 塑壳断路器 电流互感器 电容器 无功补偿自动控制器 低压防雷及浪涌保护器 低压母线 供应商名称 原产地 备注 3.5 投标人技术参数偏差表
投标人提供的产品技术规范应完全满足本技术规范中的规定。若有偏差,投标人应如实、认真地在
8
投标人技术参数偏差表(见表11)中填写偏差值,否则视为与本技术规范中规定的要求一致。若无技术偏差,则应在表11中填写“无偏差”。
表11 投标人技术参数偏差表
序号 1 2 3 项 目 对应条款编号 技术招标文件要求 差 异 备 注 3.6 投标人应提供的其他资料 3.6.1 用户运行证明
3.6.2 同类产品鉴定证书及鉴定产品的型式试验报告
投标人提供的鉴定证书表见表12。
表12 投标人提供的鉴定证书表
序号 鉴定产品型号名称 组织鉴定单位 依据标准 鉴定时间 投标人提供的试验检测报告表见表13。
试验报告类别和 内容 序号 产品型号名称 依据标准 试验时间 试验单位
表13 投标人提供的试验检测报告表
3.7 投标人需提供的设备图纸及资料
投标人应提供以下图纸及资料:
1) 电气主接线图。2) 箱变平面布置图。
9
1
因篇幅问题不能全部显示,请点此查看更多更全内容